- Programmable for Direct Transfer Trip, Permissive
Transfer Trip, Blocking and Unblocking applications
- Interchangeable communications for Audio, Digital
and Direct fiber versions
- 2 or 4 audio tone versions available
- Digital versions available
RS-449, X.21, G.703 (64kbs), and E1 (75/120 Ohm or DB15
connectors).
- Available C37.94 interface and remote Fiber
Service Unit
- Fiber version available 850nm, 1300nm, 1550nm
- Up to seven programmable functions available
on digital and fiber version
- Programmable alarm anunciator outputs
- Internal event counters
- Security/Dependability compliant to IEC 834-1
standards
- Sequence-of-events recording
- Address and Checkback testing
- Remote RS-232 programming and interrogation
- Typical Trip times: 5-17 ms (Audio) and 3 ms
(Digital & Fiber)
- Meets all applicable ANSI
and IEC standards
- The RFL 9745 is now
available with a UCA interface that supports GOOSE
messaging for LAN based tripping and alarming.
|
|
|